HV Series

Engineered for HVAC systems and air handling applications, offering multiple pressure ranges within a single device

The HV Series features a broad dynamic range, making it ideal for delivering multiple pressure ranges in a single package, thereby reducing the need for multiple sensor variants to meet the stringent functional demands of the HVAC market. Designed to measure dry air and non-aggressive gas pressures, the HV Series sets a new standard in HVAC sensor integration by incorporating amplification, ADC, DSP, and processor intelligence directly into the sensor.

Equipped with advanced Multi-Range™ technology, each sensor can support up to eight selectable pressure ranges, starting from pressures as low as 25 pascals. Additionally, the HV Series includes a 50/60Hz notch filter to reduce the impact of power noise spikes and offers optional integrated closed-loop control and advanced digital filtering features.

With its exceptionally low noise floor and stable zero point, the HV Series delivers superior accuracy, outstanding long-term stability, and minimal error rates, making it the optimal choice for HVAC systems and other air handling applications.

HVAC Applications Video

HV Series Benefits Summary

Product50/60 Hz Notch FilterPosition InsensitivityAdvanced Digital FilteringClosed Loop ControlPressure Switch
HV110-SM02
HV110-SM02
Yes
Optional
Optional
Optional
HV120-SM02
HV120-SM02
Yes
Optional
Optional
Optional
HV160-SM02
HV160-SM02
Yes
Optional
Optional
Optional
HV210-SM02
HV210-SM02
Yes
Yes
Optional
Optional
Optional
Evaluation hardware, valves and accessories
EB02
EB02
Evaluation board EB02 supports all HV Series products.
EK04-HV
EK04-HV
HV Series evaluation kit, EK04-HV, includes evaluation board and one unit of each HV Series sensor.
AZ100
AZ100
Auto zero valve provides automatic zero calibration between readings.
KP-ROR
KP-ROR
Right angle adapters for reducing total Z-height. KP-ROR includes o-rings for airtight seal (KP-RAR excludes o-rings).
ProductMulti-Range Full Scale Pressure Limits (FSS)Number of Pressure RangesUpdate RateBW Corner FrequencyAccuracy (%)Long-Term StabilityShort-Term Error BandTotal Error Band
HV110-SM02±125 Pa to ±2.5 kPa59 ms0.1 – 10 Hz0.05%2 Pa1.25 Pa4 Pa
HV120-SM02±625 Pa to ±5 kPa49 ms0.1 – 10 Hz0.05%5 Pa3 Pa10 Pa
HV160-SM02±625 Pa to ±15 kPa89 ms0.1 – 10 Hz0.05%8 Pa5 Pa15 Pa
HV210-SM02±25 Pa to ±2.5 kPa79 ms0.1 – 10 Hz0.05%1.25 Pa0.75 Pa1.75 Pa

Common Device Features: 3.3V supply
Long-Term Stability is measured after first 12 months
Short-Term Error Band (STEB) is measured over 24 hours, after auto-zero

Common Specifications

  • 16-bit resolution each range
  • Up to 19-bit effective resolution
  • Integrated 50/60 Hz notch filter
  • Optional closed loop control
  • Optional pressure switch
  • Optional advanced digital filtering
  • Temperature-compensated from 0°C to 50°C
  • Supply voltage compensation
  • Fully integrated compensation math
  • Standard I2C and SPI interfaces
Evaluation SoftwareVersionDateDownload
PRT-0279 EB02 Evaluation SoftwareEJanuary 2024
Software Download
PRT-0143 EK04-HV and EB01 Evaluation SoftwareEFebruary 2024
Software Download
Drawings and CAD FilesVersionDateDownload
SM02 Package for all HV Series Sensors (IGS and STEP files)AMarch 2023
ZIP file Download
KP-ROR Package for Right Angle Adapters (STEP file)AFebruary 2024
ZIP file Download

Download models in over 50 formats

HV Series

Target Markets

Stay informed!
Sign-up to receive the latest
HV Series updates.

Privacy Policy